Permit: T03CM04130

Parcel: 10824012A


Addresses:

2498 E RIVER RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T03CM04130

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
11/12/2004 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
09/27/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/20/2004 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*/1)CONFIRMED WITH McGETREY'S OFFICE (KEN RIDGELIY) ON REQUIREMENT THAT ALL RECEPTACLES IN PATIENT CARE AREAS WHICH INCLUDE CHAIR AND WALL RECIPTACLES NEED TO BE IN METAL RACE WAYS PER SECTION 513-13 A OF THE 99 MEL. 2)THIS NOTE HAS BEEN PUT ON PLANS AS A DELTA 1 ON SHEET E-Z 3)THE CONDUITS COMING FROM UNDERGROUND TO FEED RECEPACLES ARE IN PVC-ABOVE GROUND HCF MC OKEY
04/26/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :
The service is not per code.| 210*/ PRE-SLAB - PVC - OK.
04/23/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*/ 1) STUB UPS AT LOAD CENTER
04/21/2004 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection 0000*/ 1) PRE-SLAB PVC, OK