Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM04110

Parcel: 13329012F


Addresses:

8495 E BROADWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/08/2003 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS HAVE BEEN MADE.
10/03/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) CONDENSATE DRAINS DO NOT HAVE ADEQUATE SLOPE. PROVIDE MIN. 1/8" PER FOOT SLOPE. 2) SUPPORT REFER LINES ON ROOF NEAR CONDENSORS. RE-CALL FOR INSPECTION.