Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03CM04100

Parcel: 116277250

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/06/2004 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*/ 1) SERVICE EQUIPMENT OK TO CLEAR ELECTRIC SERVICE. SUBJECT TO BOND POSTING AND INSPECTORS SIGN OFF
07/02/2004 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) INSTALL BOND BUSHINGS OR BONDING TYPE LOCK NUTS ON 2 1/2" SECONDARY CONDUITS IN CT CAN , PER 250-94 NEC 2) INSTALL FUSES AND REJECTION PINS IN MAIN DISCONNECT SW