Permit: T03CM04095

Parcel: 13113219B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM04095

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/13/2004 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :* WATER TEST WASTE & VENT UNIT 5 &12 OK. WATER PIPING OK
09/03/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/03035-WASTE VENT THRU ROOF WATER TEST UNITS 10 & 11 OK
WATER PIPING UNITS #10 &11 OK
1)RETEST UNIT #12 NO WATER IN TEST
03050-
15PSI TEST OF UNIT #4 OK
15PSI TEST OF UNIT #10 OK
15PSI TEST OF UTILITY ROOM OK
15PSI TEST OF UNIT #6 OK
08/19/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/ 1) 15 PSI AIR TEST ON IN WALL FOR UNIT. UNIT 14 TUB WATER TEST OK
08/17/2004 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*/PARTIAL APPROVAL-GAS PIPING IN WALL ONLY PRESSURE TEST OK. ALL UNITS EXCEPT LAUNDRY, UNIT 6,UNIT 4.
1)WASTER? VENT WATER TEST THRU ROOF UNITS 10,11,12
2)RUN TEST TUB UNIT 14
3)RETEST ALL GAS PIPING WITH? UNIONS ARG ROMOVED AND ALL EXTERIOR PIPING IS COMPLETE. VALVES? INPLACE
4)HAVE 03050 & 03052 ADDED TO PERMIT CARD
05/18/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/27/2004 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*/ 1) AIR OR WTR TEST ALL PIPING. 2) SUPPORT ALL PIPING PROPERLY. 3) PROVIDE CITY APPROVED GAS ISOMETRIC FOR NATURAL GAS SYSTEM WITH PRESSURE TEST ON ALL PIPING. 4) PLEASE HAVE PLBR PRESENT AT NEXT INSP.