Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T03CM04095
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/08/2004 | ELECTRIC - UFER | Approved | ||
08/20/2004 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* | |
08/19/2004 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999*/DENIED 1.A) REVISE PLANT TO SHOW EACH APARTMENT ACCURATELY TO EACH RESPECTIVE SERVICE 1.B.) RECALL ALL INSPECTION CODES AS NECESSARY. 1.C.) ADD OTHER CODES TO PERMIT AS NEEDED. EG. TEMP POWER FINAL & TEST, TEMP C OF O, TEMP POWER CONSTRUCTION, ETC. 2) MAIN GROUNDING ELECTRODE CONDUCTOR MUST TERMINATE IN NUTRAL BAR AT SERVICE OR HAVE MAIN BONDING JUMPER APPROPRIATELY SIZED. 3) FUTURE POWER CLEARANCE WILL ONLY BE MADE WITH PLAN. IF THIS IS NOT DESIREABLE WITH TEP PLEASE MAKE PROPER ADDRESS CORRECTION WITH COUNTY ADDRESSING AND CHANGE ACCURATELY ON PERMIT AND INSPECTION REQUEST FORM. 4) PLEASE PERMANEATLY INDICATE NUMBER OF SERVICE AND WHERE THEY ARE LOCATED PER ART.230 5) RODS TO BE FLUSH OR BELOW GRADE 6) TIGHTEN ROD CLAMPS 7) THE MAIN GROUND ELECTRODE CONDUCTOR NOT TO DEPEND ON OTHER SERVICE TO MAINTAIN TAP TO EACH SERVICE (EXTERIOR) |