Permit: T03CM04095

Parcel: 13113219B

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T03CM04095

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2004 ELECTRIC - UFER Approved
08/20/2004 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
08/19/2004 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*/DENIED
1.A) REVISE PLANT TO SHOW EACH APARTMENT ACCURATELY TO EACH RESPECTIVE SERVICE
1.B.) RECALL ALL INSPECTION CODES AS NECESSARY.
1.C.) ADD OTHER CODES TO PERMIT AS NEEDED. EG.
TEMP POWER FINAL & TEST, TEMP C OF O, TEMP POWER CONSTRUCTION, ETC.
2) MAIN GROUNDING ELECTRODE CONDUCTOR MUST TERMINATE IN NUTRAL BAR AT SERVICE OR HAVE MAIN BONDING JUMPER APPROPRIATELY SIZED.
3) FUTURE POWER CLEARANCE WILL ONLY BE MADE WITH PLAN. IF THIS IS NOT DESIREABLE WITH TEP PLEASE MAKE PROPER ADDRESS CORRECTION WITH COUNTY ADDRESSING AND CHANGE ACCURATELY ON PERMIT AND INSPECTION REQUEST FORM.
4) PLEASE PERMANEATLY INDICATE NUMBER OF SERVICE AND WHERE THEY ARE LOCATED PER ART.230
5) RODS TO BE FLUSH OR BELOW GRADE
6) TIGHTEN ROD CLAMPS
7) THE MAIN GROUND ELECTRODE CONDUCTOR NOT TO DEPEND ON OTHER SERVICE TO MAINTAIN TAP TO EACH SERVICE (EXTERIOR)