Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/31/2004 | FRAMING | Approved | IVRS - Inspection :* | |
| 08/26/2004 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) NO PLANS ON SITE |
|
| 08/20/2004 | FRAMING | Not ready for Inspection | / 1) INSTALL ALL WINDOWS 2) NO PRESSURE TEST ON H20 LINE 3) NO PLUMBING PAGE IN PLAN SET 4) AT H20 HTR LEAVE SPECS FOR PRV VALVE IF NO INTERNAL BY BASS IN PRV THEN EXPANSION TANK TO BE INSTALLED 4) WHAT ARE 3/4" H20 LINES AT HVAC CLOSET FOR ? 5) FILL TUBS WITH H20 AND LOOSE TRUSS GUSSETT PREPARED 7) OVER SPAN STUD SPACE AT REFRIGERATOR H20 8) LATH INSTALLED, NO SERVICE PANEL 9) NO ELECTRIC PLAN 10) NEED DETAIL PLAN FOR HVAC |