Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 02/23/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 02/13/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) FRONT PATIO POSTS NOT INSTALLED |
| 02/11/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*1) TRUSSES MUST BE SHIMMED TO PROVIDE FULL BEARING AT BEARING POINTS 2) DOUBLE 2X POSTS REQUIRED EACH END OF GIRDER TRUSSES 3) PORCH POSTS NOT IN; POST FOOTINGS NOT IN OR INSPECTED DO NOT POUR 4) BEAM CONDITIONS NOT PER PLAN 5) HIP TRUSSES MISSING HANGERS 6) HEADERS MUST BEAR ON TRIMMERS 7) CROSS BRACE TRUSSES BACK END & EVERY 25 FT 8) MANY AREAS OF ROOF NOT NAILED |
| 02/10/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED SHEAR WALL PLAN-DETAILS |