Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM04081
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
10/09/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/ 1) PLEASE PROVIDE SEPARATE BACK FLOW DEVICES FOR EACH PIECE OF EQUIPMENT SERVED. ESPRESSO AND COFFEE MACHINE EACH REQUIRE SEP. BACKFLOW PROTECTION. CAN BE 007. 2) INLET TO ICE MACHINE BACKFLOW DEVICE SHALL BE SAME SIZE AS UNIT SERVED. 3) ALL INDIRECT WASTE PIPING SHALL TERMINATE AT LEAST 1" ABOVE FLOOR SINKS. 4) ICE BIN STORAGE DRAIN REQUIRES CLEAN OUT AND PROPER SUPPORT. 5) WOMENS RESTROOM H/C STOOL TO HAVE FLUSH HANDLE ON WIDE SIDE OF ROOM. 6) LAVS IN RESTROOMS TO HAVE H/C DRAIN AND HOT SUPPLY INSULATION COVERS. | |
09/19/2003 | PLUMBING - FINAL | Not ready for Inspection |