Permit: T03CM04081

Parcel: 12810082B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T03CM04081

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
09/19/2003 PLUMBING - INTERMEDIATE Approved IVRS - Inspection 0000*/ 1) PLUMBING INTERMEDIATE WASTE AND VENT THRU ROOF WATER TEST OK TO BACKFILL 2) PLEASE PROVIDE PERMANENT CAP IN EXISTING GAS VALVE AT HOOD 3) PLEASE PROVIDE CORRECT SIZE FLOOR SINK PRIOR TO CONCRETE PLACEMENT 4) PLEASE CHECK AND VERIFY 1" AIR GAP AT ICE MACHINE OR PROVIDE CORRECT RPB. ALSO PROVIDE CORRECT RPB FOR ALL COFFEE MAKERS