Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM04081
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) PLUMBING INTERMEDIATE WASTE AND VENT THRU ROOF WATER TEST OK TO BACKFILL 2) PLEASE PROVIDE PERMANENT CAP IN EXISTING GAS VALVE AT HOOD 3) PLEASE PROVIDE CORRECT SIZE FLOOR SINK PRIOR TO CONCRETE PLACEMENT 4) PLEASE CHECK AND VERIFY 1" AIR GAP AT ICE MACHINE OR PROVIDE CORRECT RPB. ALSO PROVIDE CORRECT RPB FOR ALL COFFEE MAKERS | |
09/17/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) A DOUBLE WYE MAY NOT LAY ON ITS BACK. 2) SUPPORT ABS MIDSTORY. 3) ALL HORIZONTAL OVERHEAD PIPING TO BE INSTALLED TO INSTALLATION STANDARD AND TABLE 3-1, 94 UPC. |