Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2003 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/10/2003 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/ 1) SUPPORT M/C CABLE W/IN 12" OF BOXES WHERE USED 2) WHERE BLUE MC IS USED IN EXAM ROOMS IF MUST BE OF THE HCF TYPE OR EMT |