Permit: T03CM04073


Addresses:

4380 E 22ND ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM04073

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2003 PLUMBING - FINAL Approved IVRS - Inspection 0000*
11/07/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE HAVE ALL GAS APPLIANCES INSTALLED OR GAS VALVES PLUGGED. 2) PLEASE PROVIDE MIN. 1" AIR GAP AT ALL INDIRECT WASTES AT FLOOR SINKS AND DRAINS. 3) PLEASE PROVIDE RPB FOR CARBONATER AT ACCESSABLE LOCATION. 4) PLEASE PROVIDE CITY APPROVED STAMPED DRAWING FOR INDIRECT WASTE MANIFOLDING AT HOT AND COLD STORAGE BIN LOCATIONS OR PROVIDE SEPERATE INDIRECT WASTES FOR EACH BIN. 5) ALL NEW CONSTRUCTION INDIRECT WASTE TO BE PROVIDED WITH CLEAN OUTS AT APPROPRIATE LOCATIONS. 6) ICE MACHINE DRAINS TO BE PROVIDED FROM EACH UNIT SEPERATLY NOT MANIFOLDED TOGETHER. 6.5) NO TAMPERING VALVE ON 140 DEGREE HOT WATER FOR PUBLIC SYSTEM. 7) PLEASE PROVIDE DOCUMENTATION OF CERT. OF RPBS. WITHIN THE LAST YEAR FOR ALL ON SITE. 8) GARBAGE DISPOSAL DRAIN TO GO TO DIRECT SANITARY WASTE.
11/06/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/1) GREASE DRAIN FOR ROOF TOP EXHAUST HOODS WATER TEST OK. 2) GAS PIPING TO BE INSTALLED PER REVISED PLAN. 3" PIPING GAS TO SUPPLY EXISTING SYSTEM WITH APPROVED SHUT OFF VALVE, 1-1/4" TO SUPPLY NEW SYSTEM WITH APPROVED SHUT OFF VALVE.