Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/15/2009 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 02/18/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE 1 HR PROTECTION ON 2 X 8 FIREWALL 2) NEED RECEPT TO BE GFCI PROTECTED 3) NEED PROPER CLEARANCE IN FRONT OF NEW SUB PANEL PER CODE |
|
| 02/10/2009 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVISED PLANS DO NOT MATCH FIELD ? |
|
| 09/22/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EAST SIDE 9' HIGH 2) WEST SIDE 9'-9" HIGH 3) NEED PLANS AND INSPECTIONS FOR ADDITIONAL HEIGHT 4) HAVE APPROVED PLANS AND CORRECTIONS PRIOR TO NEXT INSPECTION OR REFEE WILL APPLY |
|
| 01/03/2008 | BUILDING - FINAL | Denied | PLANS DO NOT INCLUDE PONY WALLS ON MASONRY. BUILDING HAS EXCEEDED APPROVED HEIGHT. CORRECT REVISIONS REQUIRED!!! | |
| 12/03/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAX HEIGHT OF STRUCTURE VARIES CONSIDERABLY FROM APPROVED PLAN. HAVE ZONING APPROVE CHANGES 2) ELECTRIC RECEPTACLES STILL NOT GFI PROTECTED 3) LANDING OUTSIDE DOOR NOT CONSTRUCTED |
|
| 06/05/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LABEL SUB PANEL CIRCUITS 2) LABEL MAIN SERVICE CIRCUITS 3) PER PLAN STORAGE CIRCUITS GFCI PROTECTED 4) COMPLETE PONY WALL WEST AND GABLE WALLS 5) BLANK COVER NEEDED DEAD FRONT MAIN SERVICE PANEL 6) DIRT FLOOR ? |