Inspection History Details
Permit: T03CM04068
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*/ 1) OK FINAL | |
| 11/15/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ 1) BOND GROUNDING EQUIPMENT CONDUCTOR TO SUPLEMENTAL GROUNDING ELECTRODE 2) CONDUCTOR TO BE COLOR CODED TO VOLTAGE SUPPLIED 3) NEED ACCESS TO POLE HEADS FOR INSPECTION 4) DISCONNECTING MEANS NEEDED PER TAP RULSE 240.21 5) GROUNDING ELECTRODE CONDUCTOR AND BONDING JUMPER TO BE SAME TERMINAL-CNNNOT BE PATH OF RETURN 6) LABEL PANEL COVER 7) AT MAIN SERVICE DISCONNECT GROUNDED TERMINAL AND GROUNDING TERMINAL TO BE BONDED |