Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/12/2003 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/11/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ LOOKS GOOD. 1) COMPLETE GAS PIPING. 2) TERMINATE CONDENSATE PIPING WEST OF ELECT SERVICE ENTRANCE. NO SIDEWALKS, PAVED PARKING LOTS, ETC. |
| 11/26/2003 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) IMC SEC 306.6 SLOPED ROOF, 4/12 PITCH OR GREATER, A LEVEL PLAT FORM TO ACCESS UNIT FOR SERVICE/ REPAIR IS NECESSARY. 2) GAS LINE PRESS TEST-8 PSI. NEED TO CHECK- REPRESSURIZE LINE AGAIN. |