Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM04030
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2003 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK. 2) WASTE AND VENT SYSTEM IS OK. 3) OVERHEAD WATER DISTRIBUTION IS OK. 4) OK FOR DRYWALL. | |
09/19/2003 | PLUMBING - INTERMEDIATE | Partial Approval | 1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN OK. 3) OK TO BACKFILL TRENCH. | |
09/18/2003 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/1) 4" VERTICAL WASTE HAS A 1/4 BEND AND REQUIRES AN L-SWEEP. 2) RETEST SYSTEM. 3) MUST SECURE OR PROVIDE HANGERS EVERY 4" ON 2ND FLOOR 3" HORIZONTAL WASTE. | |
09/08/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/ 1) MEN'S AND WOMEN'S RESTROOM COPPER-OK 2) OK TO COVER BATHROOM WALLS UP TO 4" VTR, NEED TO SEE 4" ABS VTR 3) CLOSE FLANGES THIS AREA-OK | |
09/05/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
08/26/2003 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000*/ 1) APPROVED PLANS CALLS P-8 TO BE A 3" TRAP 2) APPROVED PLANS DOES NOT SHOW 2" FLOOR DRAINS IN RESTROOM 3) NOTE: WILL REQUIRE A REVISED AN APPROVED DRAWING ON PLUMBING ISOMETRIC SHOWING CENTER OUTLET TO P.O.C. PRIOR TO FINAL INSPECTION | |
08/22/2003 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK. 3) THIS INSPECTION IS FOR MENS AND WOMENS RESTROOMS #117 AND #118. 4) OK TO BACKFILL. |