Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2003 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000*/ 1) SOIL WATER TEST IS OK. 2) WASTE AND VENT SYSTEM IS OK. 3) OVERHEAD WATER DISTRIBUTION IS OK. 4) OK FOR DRYWALL. |
| 09/19/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN OK. 3) OK TO BACKFILL TRENCH. |
| 09/18/2003 |
PLUMBING - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0999*/1) 4" VERTICAL WASTE HAS A 1/4 BEND AND REQUIRES AN L-SWEEP. 2) RETEST SYSTEM. 3) MUST SECURE OR PROVIDE HANGERS EVERY 4" ON 2ND FLOOR 3" HORIZONTAL WASTE. |
| 09/08/2003 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) MEN'S AND WOMEN'S RESTROOM COPPER-OK 2) OK TO COVER BATHROOM WALLS UP TO 4" VTR, NEED TO SEE 4" ABS VTR 3) CLOSE FLANGES THIS AREA-OK |
| 09/05/2003 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/26/2003 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) APPROVED PLANS CALLS P-8 TO BE A 3" TRAP 2) APPROVED PLANS DOES NOT SHOW 2" FLOOR DRAINS IN RESTROOM 3) NOTE: WILL REQUIRE A REVISED AN APPROVED DRAWING ON PLUMBING ISOMETRIC SHOWING CENTER OUTLET TO P.O.C. PRIOR TO FINAL INSPECTION |
| 08/22/2003 |
PLUMBING - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000*/1) SOIL WATER TEST IS OK. 2) P.O.C. OF NEW BLDG DRAIN TO EXISTING BLDG DRAIN IS OK. 3) THIS INSPECTION IS FOR MENS AND WOMENS RESTROOMS #117 AND #118. 4) OK TO BACKFILL. |