Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM04030
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
01/02/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ OK TEMP C OF O. 1) EXTEND RECEPT FLUSH WITH FINISHED WALL, USE LISTED EXTENSION RING, ROOM #129 SOUTH WALL. 2) INSTALL DISC. S.W. FOR NEW H2O HTR IN JANITORS CLOSET | |
12/29/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920*/ BLDG LOCKED. | |
12/24/2003 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ TO BE RESCHEDULED FOR 12/29/03 | |
12/09/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) UPDATE ALL PANELS TO REFLECT CIRCUITS SERVING PANELS MISSING PARTS THRU-OUT BLDG. UPDATED PANEL SCHEDULES TO BE IN APPROVED HOLDER, STICK ON LABELS (FILE LABELS) NOT ACCEPTABLE 2) SUPPORT CONDUITS IN UTILITY CLOSET AT STAIR WAY 3) FIRE ALARM SYSTEM NOT OPERABLE YET 4) REVISE PLANS TO REFLECT ACTUAL INSTALLATION | |
12/08/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*/ 1) BOX FOR RECEIPTS BY FRONT DESK NEEDS KO PLUGS. 2) MISSING COVER ON J-BOX AT NORTH BREAK AREA. 3) PANEL BY FRONT WINDOW NEEDS KO PLUG, BREAKER BLANKS. 4) COMPUTER ROOM [NORTH] QUARTZ LIGHT NOT WIRED PROPERLY. SUPPORT MC TO STRUCTURE. 5) COVERS TO BOXES MISSING THRU OUT BLDG. 6) NEED UPDATED AND APPROVED PLANS. 7) UPDATE ALL PANEL SCHEDULES. | |
09/04/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* OK TEMP C OF O FOR ALL AREAS EXCEPT RM # 112, 113, 114, 116 |