Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2004 | ELECTRIC - TEMP POWER FOR TEST | Approved | ||
| 09/16/2004 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :*/ 1) INSTALL SECONDARY FEEDERS AND MAKE-UP IN CT CAN. | |
| 09/14/2004 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/NOTES: 1)BOND NEUTRALS IN SERVICE DISCONNECTS PER NOC. 250 & 230 2)INSTALL FUSES & REJECTION PINS 3)PERMANENT ADDRESS LABEL ON SERVICE & LABEL DISCONNECTS 4)REVISE PLANS TO REFLECT FIELD INSTALLATION OF FEEDERS TO MCC 5)BOND X-FORMER TO WATER LINES OR VERITY BONDING |