Permit: T03CM04028

Parcel: 120086690


Addresses:

320 W IRVINGTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
11/03/2004 ELECTRIC - TEMP POWER FOR TEST Approved
09/16/2004 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*/ 1) INSTALL SECONDARY FEEDERS AND MAKE-UP IN CT CAN.
09/14/2004 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*/NOTES: 1)BOND NEUTRALS IN SERVICE DISCONNECTS PER NOC. 250 & 230 2)INSTALL FUSES & REJECTION PINS 3)PERMANENT ADDRESS LABEL ON SERVICE & LABEL DISCONNECTS 4)REVISE PLANS TO REFLECT FIELD INSTALLATION OF FEEDERS TO MCC 5)BOND X-FORMER TO WATER LINES OR VERITY BONDING