Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2004 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/29/2004 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ 1) MC CABLE NOT CONSIDERED SUPPORTED WHEN TIED TO OTHER CABLES, MUST BE SUPPORTED TO STRUCTURE. 2) PLUG UNUSED OPENING IN FIXTURES. 3) SEE NOTES LAST INSP. |
|
| 06/25/2004 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) PROTECT M/C CABLE AT SHALLOW STUDS. 2) SUPPORT M/C CABLE WITHIN 12" OF CANS AND BOXES THHN AND TO OTHER CABLES NOT ALLOWED. 3) TIGHTEN CONDUIT FITTINGS. 4) CHASE NIPPLE NOT AN APPROVED FITTING AT LB. 5) CONDUIT RUNS NOT TO EXCEED 360o IN A RUN. | |
| 05/20/2004 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ PARTIAL OFFICE. |