Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T03CM04019
Inspection Description - FRAMING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/13/2004 | FRAMING | Approved | IVRS - Inspection 0000* | |
| 04/12/2004 | FRAMING | Partial Approval | IVRS - Inspection 0000*/ 1) GAS LINE NOT IN 2) NO DWV WATER TEST | |
| 04/08/2004 | FRAMING | Denied | IVRS - Inspection 0999*/ 1) NO DWV WATER TEST 2) PROVIDE 1" CLEARANCE TO FURNACE 'B' VENT 3) SHOWER/TUB VALVE MISSING 4) WIRES TRAPPED HALL/KITCHEN 5) POST 3-2 X PORCH GLB AT DINING ROOM 6) FIRE BLOCK BACK WALL FIRE PLACE 7) DRYER VENT CANNOT HAVE MESH T CAP 8) GAS LINES NOT IN |