Permit: T03CM04017

Parcel: 140105980

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
09/26/2003 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection 0000*
09/25/2003 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*/ 1) DOUBLE 2 X 8 BEAM AT ENTRY NOTCHED GREATER THAN 25 PERCENT 2) HOUSE NOT CLIPPED 3) #3 SHEAR NOT NAILED PER PLAN 4) 6/DT1 NOT COMPLIED WITH AT 48" ON CENTER-NOT NAILED THRU OSB 5) OSB REQUIRES 1/8" END AND EDGE CLEARANCE 6) OSB MUST HAVE END ON TRUSS NOT SLAB
09/24/2003 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection 0000*/ 1) CANCELLED