Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/11/2003 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 12/10/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NO CHANGE |
| 12/08/2003 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) WHITE CONDUCTOR NOT ALLOWED TO BE HOT IN ELECTRIC PANEL 2) A/C CIRCUIT BREAKER ALUMINIUM CONDUCTOR REQUIRES ANTI-CORROSIVE GREASE AND ALUMINIUM GROUNDS REQUIRE ANTI-CORROSIVE GREASE 3) 1" CLEARANCE REQUIRED TO COMBUSTIBLES FOR FURNACE "B" VENT 4) ATTIC SWITCH COVER BROKEN 5) BATHROOM GFCI HOT WHEN TRIPPED |