Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/16/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ 1) OK FOR FINAL C OF O 2) ALL CORRECTIONS HAVE BEEN MADE |
| 04/14/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 3/8" I.D. GAS FLEX CONNECTORS NOT ADEQUATE FOR 100,000 BTU. SEE LISTING ON FLEX. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE. TIGHTEN LOOSE SEAL TITE FIITINGS ON EQUIPMENT ON ROOF. PROVIDE A BLOCK AND CLAMP ON SHORT HORIZONTAL SECTION OF GAS PIPE ON ROOF. PROVIDE COIL GUARDS ON A/C UNITS AS PER PLANS. PROVIDE 2" FILTERS AS PER PLANS. |