Permit: T03CM04009

Parcel: 13605313K

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/16/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ 1) OK FOR FINAL C OF O 2) ALL CORRECTIONS HAVE BEEN MADE
04/14/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 3/8" I.D. GAS FLEX CONNECTORS NOT ADEQUATE FOR 100,000 BTU. SEE LISTING ON FLEX. EXTEND SEWER VENT 2' ABOVE FRESH AIR INTAKE. TIGHTEN LOOSE SEAL TITE FIITINGS ON EQUIPMENT ON ROOF. PROVIDE A BLOCK AND CLAMP ON SHORT HORIZONTAL SECTION OF GAS PIPE ON ROOF. PROVIDE COIL GUARDS ON A/C UNITS AS PER PLANS. PROVIDE 2" FILTERS AS PER PLANS.