Permit: T03CM04009

Parcel: 13605313K

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/20/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/ CORRECTION MADE - 2 BACKFLOW CERTIFICATIONS TURNED IN.
04/19/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 15 PSI TEST ENTIRE SYSTEM, CORRECTION MADE ON ROOF TOP FOR FLEXES OK. CORRECTION MADE TO WTR HTR PIPING OK. NEED BACKFLOW CERTIFICATIONS FOR FINAL. GAS CARD AT METER PER BOND POSTED.
04/14/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) INSTALL WTR HTR TO APPROVED PLAN - PIPING. 2) BACKFLOW PROTECTION - TESTABLE DEVISE - WILL BE REQUIRED FOR LANDSCAPING WTR SUPPLY. 3) WILL NEED CERTIFICATION OF BACKFLOW DEVICES FOR FINAL. 4) PROVIDE PROPER SUPPORT AND CLAMPS AT BOTH GAS SUPPLIES TO ROOF TOP UNITS. 5) PROVIDE RATED FLEX OR RIDGID PIPE ROOF TOP UNITS.