Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/28/2004 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/24/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/10/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999* | |
| 02/06/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection 0000* | |
| 01/30/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection 0999*/ 1) PLUMBING IS NOT PER PLAN BUILD TO PLAN OR REVISE PLAN TO AS BUILT AND APPROVED BY CITY 2) TUB IS NOT PROPERLY VENTED MUST VENT WITHIN 60" OF TRAP ON 2" DRAIN PRESENTLY 71" TO VENT 3) FLAT VENT MUST CONNECT ABOVE THE CENTER LINE OF CONNECTING DRAIN |