Permit: T03CM03992

Parcel: 118040390

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
10/18/2004 BUILDING - FINAL Approved IVRS - Inspection :*
10/12/2004 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) NO ADDRESS ON HOUSE 2) ROOF MOUNTED GFCI OUTLET MUST BE MOUNTED TO NOT ROTATE AROUND CONDUIT 3) SECURE A/C PLATFORM TO ROOF STRUCTURE MINIMUM 1/4" BOLTS 4) WEATHER TIGHT CONNECTORS LOOSE ON A/C 5) A/C AND PANEL CANNOT HAVE HOT WIRES. COLOR CODED WHITE 6) ELECTRIC OUTLET CANNOT BE UNDER COUNTER WITH OVERHANG GREATER THAN 6" 7) MASTER BATH TOILET HAS LESS THAN 15" SIDE CLEARANCE TO VANITY FROM TOILET 8) PROVIDE CENTER LINE INSULATION AND STUCCO INSTALLATION CERTIFICATES 9) WHERE IS ATTIC ACCESS ?