Permit: T03CM03984

Parcel: 118050490

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
02/27/2004 FRAMING Approved IVRS - Inspection 0000*
02/12/2004 FRAMING Denied IVRS - Inspection 0999*/ 1) A01 AND A03 TRUSSES HAVE BEEN INSTALLED INCORRECTLY-REQUIRES ENGINEERED FIX 2) STRAP TOP PLATE 3) FIRE STOP AC SHAFT TO ATTIC NEAR GARAGE 4) NAIL PLATE THROUGHOUT 5) SLEEVE CONDUCTORS THROUGH MASONRY 6) PROTECT CONDUCTORS AT SHARP EDGES 7) CONNECT FAN DUCT IN HALL BATH 8) NAIL PLATE A/C LINES AT TOP PLATE 9) INSTALL CLAPPERS AT EXHAUST FANS 10) INSTALL COMBUSTION AND RETURN 11) REVISE MECHANICAL AS BUILT 12) EXTEND DRY EXHAUST AT ROOF JACK 13) PROVIDE 1/4" SLOPE AT KITCHEN TRAP ARM 14) REVISE WATER LINE TO MATCH AS-BUILT 15) SEPARATE WATER LINE AT ROOF SHEATHING
01/22/2004 FRAMING Not ready for Inspection IVRS - Inspection 0000*