Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/22/2004 |
PLUMBING - INTERMEDIATE |
|
Approved |
IVRS - Inspection :*/1)BACKFLOW CERTIFICATION FOR BUILDING SERVICE 2)BACKFLOW CERTIFICATON FOR IRRIGATION. |
| 03/25/2004 |
PLUMBING - INTERMEDIATE |
|
Partial Approval |
IVRS - Inspection 0000*/ WTR TEST ON WASTE AND VENT THRU ROOF OK. H20 PIPING OK. 3" VENT IN RESTROOM WILL REQUIRE 3" UPPER TERMINAL C.O. TO BE ACCESSABLE. WILL VIEW AT FINAL. WRAP GAS PENETRATION THRU WALL. WTR HTR TO BE BELOW 8' OR REQUIRE PERMANENT LADDER AND PLATFORM FOR SERVICE. COFFEE MAKER MAY REQUIRE BACKFLOW DEVICE. |