Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
| Date |
Description |
Inspector |
Results |
Comments |
| 02/27/2004 |
STEM WALL/RETAINING WALL |
|
Approved |
IVRS - Inspection 0000* |
| 12/23/2003 |
STEM WALL/RETAINING WALL |
|
Partial Approval |
IVRS - Inspection 0000* 1) OK TO POUR. 2) STEM TO BE BLOCKED OUT @ OPENINGS TO ALLOW FOR INSERTION OF #4 BENT BAR PER RFI 102 12-22-03 SKI |
| 12/18/2003 |
STEM WALL/RETAINING WALL |
|
Denied |
IVRS - Inspection 0999* 1) ACI 318 REQUIRES 1" MIN SPACING BETWEEN ADJACENT BARS. 2) GSN'S REQUIRE 57 BAR DIAMETER TENSION LAP SPLICES IN CONCRETE ( 28 1/2" FOR #4 BARS IN STEM). 3) DETAIL 102/S4 FOR OPENINGS REQUIRE SLAB DOWELS FROM FOOTING @ 24" OC.. YOU ARE MISSING ALL BENT BARS AND SOME VERTICALS. 4) SPEC INSP REPORT BY JULIAN VALDEZ OF GRENIER ENG IS NOT ACCEPTED! |