Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T03CM03951
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/27/2004 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection 0000* | |
12/23/2003 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* 1) OK TO POUR. 2) STEM TO BE BLOCKED OUT @ OPENINGS TO ALLOW FOR INSERTION OF #4 BENT BAR PER RFI 102 12-22-03 SKI | |
12/18/2003 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection 0999* 1) ACI 318 REQUIRES 1" MIN SPACING BETWEEN ADJACENT BARS. 2) GSN'S REQUIRE 57 BAR DIAMETER TENSION LAP SPLICES IN CONCRETE ( 28 1/2" FOR #4 BARS IN STEM). 3) DETAIL 102/S4 FOR OPENINGS REQUIRE SLAB DOWELS FROM FOOTING @ 24" OC.. YOU ARE MISSING ALL BENT BARS AND SOME VERTICALS. 4) SPEC INSP REPORT BY JULIAN VALDEZ OF GRENIER ENG IS NOT ACCEPTED! |