Permit: T03CM03951

Parcel: 134090140


Addresses:

8450 E BROADWAY BL

Inspection Status: Approved

Inspection History: STEM WALL/RETAINING WALL

Date Description Inspector Results Comments
02/27/2004 STEM WALL/RETAINING WALL Approved IVRS - Inspection 0000*
12/23/2003 STEM WALL/RETAINING WALL Partial Approval IVRS - Inspection 0000* 1) OK TO POUR. 2) STEM TO BE BLOCKED OUT @ OPENINGS TO ALLOW FOR INSERTION OF #4 BENT BAR PER RFI 102 12-22-03 SKI
12/18/2003 STEM WALL/RETAINING WALL Denied IVRS - Inspection 0999* 1) ACI 318 REQUIRES 1" MIN SPACING BETWEEN ADJACENT BARS. 2) GSN'S REQUIRE 57 BAR DIAMETER TENSION LAP SPLICES IN CONCRETE ( 28 1/2" FOR #4 BARS IN STEM). 3) DETAIL 102/S4 FOR OPENINGS REQUIRE SLAB DOWELS FROM FOOTING @ 24" OC.. YOU ARE MISSING ALL BENT BARS AND SOME VERTICALS. 4) SPEC INSP REPORT BY JULIAN VALDEZ OF GRENIER ENG IS NOT ACCEPTED!