Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/27/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/24/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0950* |
| 10/22/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0950*/ 1) NOT COMPLETE 2) SEAL VAPOR BARRIER 3) PROVIDE SHEAR NAILER IN PANTRY 4) NAIL PROTECT COPPER 5) NO RISER OR UFER 6) SHEAR WALL BROKEN 7) PROVIDE DETAIL 27/S1.2 AZ STAIRS 8) FIRE BLOCK STAIRS 9) TOO MANY ITEMS, STOPPED INSPECTION |
| 10/21/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) AB'S MISSING WHERE MARKED, ORANGE 2) FIRE BLOCK MISSING AT WATER HEATER 3) VENT FLEX AT EXHAUST BY GARAGE BATH, NOT CONNECTED 4) CHECK LOOSE BOLTS THRU-OUT 5) NO TEST ON GAS LINE 6) STOPPED INSPECTION |