Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 10/15/2003 |
FRAMING |
|
Approved |
IVRS - Inspection 0000* |
| 10/14/2003 |
FRAMING |
|
Denied |
IVRS - Inspection 0999*/ 1) HOLDOWN AT GARAGE SHEAR WALL DAMAGED, REPLACE-BENT 2) WATER EVERY WHERE. PROBABLE LEAK, REMOVE ALL WATER 3) STUD MISSING AT GARAGE-OVERSPAN 4) LEAK AT MASTER BATH ? PEX-WET 5) HOLDOWN AT BEDROOM SHEAR WALL WRONG LOCATION. IT GOES AT END OF WALL 6) SEAL ALL VAPOR BARRIER PENETRATIONS 7) REVERSE PITCH ON A/C CONDENSATE. UNABLE TO COMPLETE INSPECTION DUE TO STOCKING OF DRYWALL. DO NOT INSULATE/DRYWALL. NEXT FAILURE WILL BE CHARGED A REINSPECTION FEE |
| 10/13/2003 |
FRAMING |
|