Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/30/2003 |
PLUMBING - ROUGH, SOIL |
|
Approved |
IVRS - Inspection 0000* |
| 10/29/2003 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) WRAP ALL ABS AND COPPER PLUMBING THAT WILL BE IN CONTACT WITH CONCRETE OR PROVIDE SLEEVES TO PREVENT CONTACT. OK TO BACKFILL PLUMBING-DO NOT PLACE CONCRETE CALL FOR A PRESLAB INSPECTION. CODE 01015 AND UFER 02005 2) IF YOU ARE GOING TO RELOCATE YOUR ELECTRIC PANEL THEN INSTALL A UFER GROUND #4 SOLID WIRE CONNECTED TO ONE OF THE 20 FEET REBAR IN FOUNDATION WIRE NEEDS TO BE LONG ENOUGH TO CONNECT TO THE NEW PANEL WITHOUT SPLICES |