Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T03CM03929
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/13/2003 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000* | |
10/10/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999* | |
10/09/2003 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*/1) REST ROOMS LAVS TO COMPLY TO ADA CLEARANCES. STOOL IN DOOR #3 TO COMPLY TO ADA SIDE WALL CLEARANCES. 2) ALL DRAINS IN EXCESS OF 135 DEGREE CHANGE OF DIRECTION TO HAVE CLEAN OUTS. 3) ALL DRAINS TO HAVE MIN. 1" CLEARANCE FOR AIRGARET FLOOR SINKS. 4) CUP SINK AT JUICE COUNTER TO BE FULL SIZE WITH CLEANOUTS. 5) JUICE MACHINES SHALL REQUIRE BACKFLOW PROTECTION INDIVIDUALLY OR HAVE AIR GAP THAT IS PROVEN. 6) PLEASE SEE SECTION 610.2 94 UPC CONCERNING INLET AND OUTLET PIPING TO WATER FILTER. THIS MAY NOT BE A COMPLETE LIST. |