Permit: T03CM03928

Parcel: 13316037K

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/22/2003 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection 0000*
08/15/2003 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*/ 1) OK WALLS SUBJECT TO INFORMATION FROM ARCHITECT 2) REGARDING CIRCUTING OF PANELS #3 PREVIOUS INSPECTION
08/14/2003 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*/ 1) PROPERLY M/C CABLE TO STUDS AND WITHIN 12" OF BOXES AND FITTINGS 2) PROTECT M/C CABLE WHERE LESS THAN 1 1/4" FROM EDGE 3) RECEPTACLES ON SOUTH WALL HAVE BEEN ADDED. HAVE PLANS REFLECT THESE OUTLETS AND CIRCUTRY. PLANS NEED TO ALSO REFLECT CIRCUITS BEING RUN OR INSTALL AS PER PLANS