Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2005 | ELECTRIC - UNDERGROUND | Approved | ||
| 04/27/2004 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) YOU MUST OBTAIN A CABLE DROP AND TEMPORARY SERVICE PERMIT FROM 201 N STONE DEVELOPMENT SERVICES 2) UFER GROUND WAS NOT INSPECTED BY CITY INSPECTOR. YOU MUST INSTALL TWO EACH 8' GROUND RODS AT LEAST 6 FEET APART CONNECTED TO THE SERVICE PANEL WITH A CONTINOUS #4 SOLID CONDUCTOR |