Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2005 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :$ 1) CORRECTIONS MADE OK 2) OK TO COVER ALL AREAS |
|
| 08/02/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/01/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) ROOF DRAINS OK 2) REQUIRE 2 X PIPE DIAMTER FROM WEIR AT TRAP TO POINT OF VENT 3) REMEMBER TRAP ARMS EXCEEDING 90 DEGREE WILL REQUIRE A CLEANOUT ON FINAL 4) SEWER/HCS APPROVED ON 5/18/05 |
|
| 07/29/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NO CHANGE FROM LAST INSPECTION |
|
| 07/27/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) VERTICAL PIPING TO HAVE MID STORY SUPPORTS 2) HORIZONTAL PIPING TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, AND THEN NO MORE THAN FOUR FEET BETWEEN HANGERS FOR ABS |
|
| 07/25/2005 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NOT READY FOR INSPECTION |