Permit: T03CM03886

Parcel: 115024840


Addresses:

422 E ADAMS ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T03CM03886

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/09/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ALL EXTERIOR/GARAGE RECEPTACLES NEED GFI PROTECTION AND SOME ARE DEAD -- NEC 210.8
2. NEED ARC FAULT PROTECTION FOR BEDROOM OUTLETS -- NEC 210.12
3. BATH GFI'S NOT WORKING
4. MAX LENGTH DISHWASHER CORD 4' -- 422.16
GO THROUGH UNITS TO CHECK THESE ITEMS AND MAKE SURE CKTS ARE WORKING PROPERLY
IDENTIFY ALL UNITS WITH ADDED HEAT STRIPS