Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM03886
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/09/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ALL EXTERIOR/GARAGE RECEPTACLES NEED GFI PROTECTION AND SOME ARE DEAD -- NEC 210.8 2. NEED ARC FAULT PROTECTION FOR BEDROOM OUTLETS -- NEC 210.12 3. BATH GFI'S NOT WORKING 4. MAX LENGTH DISHWASHER CORD 4' -- 422.16 GO THROUGH UNITS TO CHECK THESE ITEMS AND MAKE SURE CKTS ARE WORKING PROPERLY IDENTIFY ALL UNITS WITH ADDED HEAT STRIPS |