Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
Permit Number - T03CM03886
Inspection Description - ELECTRIC - TEMPORARY POLE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2006 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection :* | |
07/27/2006 | ELECTRIC - TEMPORARY POLE | Denied | 1. PROPERLY BOND SERVICE RISER 2. IN SUB-PANELS TIGHTEN ALL FEEDER TERMINATIONS AND LUG SCREW FOR NEUTRAL IN EAST UNIT. ALSO, CAN'T HAVE DIFFERENT SIZE EQUIPMENT GROUNDS UNDER SAME SET SCREW ON GROUND BAR. 3. GROUND FEEDER J-BOX AND MAKE ACCESSIBLE |
|
07/26/2006 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UFER TO BE TIED INTO NEUTRAL PRESENTLY TIED INTO GROUND BAR ONLY |