Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 12/15/2004 |
PLUMBING - FINAL |
|
Approved |
IVRS - Inspection :*/(3) BACKFLOW CERIFICATIONS TURNED IN |
| 12/08/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/CORRECTIONS MADE, REVISED & REDLINE & CITY APPROVED DRAWINGS ON SITE. 1)PROVIDE BACKFLOW CERTIFICATION FOR LANDSCAPING BACKFLOW PROTECTION FOR DEGREASER ON WALL IN WASH BAY. 3)PROVIED BACKFLOW CERTIFICATION FOR H2O MAIN SUPPLY TO BLDG. AND BACKFLOW CERTIFICATION FOR IN HOUSE PRESSURE WASHER WITH CHEMICAL ADDITION |
| 11/15/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/CALL IN ALL INSPECTIONS THAT HAVE NOT BEEN APPROVED 1)PROVIDE VACUUM BREAKER ON ACC HOSE BIBS 2)PROVIDE CLEAN OUT PLUG & COVER AT WASHING MACHINE 3)PROVIDE CORRECT BACKFLOW PROTECTION FOR CHEMICAL ADDITION. PRESSURE WASHER WITH CERTIFICATION 4)SEE NOTES FROM 5/20/04 INSPECTION 5)HAVE RED LINES ON JOB 6)HAVE ALL BACK FLOW CERTIFICATIONS. (COPIES FOR TURN IN) |
| 07/19/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :*/ 1) NO PROBLEM FOR TEMP C OF O 2) NEED ALL CORRECTIONS LISTED ON THESE SHEETS FOR FINAL AND COMPLETION OF ALL WORK 3) DRYER VENT TO TERMINATE TO DAYLIGHT |
| 07/14/2004 |
PLUMBING - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* |