Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2004 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 06/17/2004 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :*/ OK 1ST FLOOR, NO ACCESS TO 2ND FLOOR DUE TO FLOORING INSTALL. | |
| 06/16/2004 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*/ SIESMIC WIRES USED TO SUPPORT BOXES AND RACEWAYS - MUST BE TIED OF BOTH ENDS. 300-11 NEC. |