Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T03CM03878
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2004 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*/ 1) OK FOR FINAL C OF O | |
08/09/2004 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) FINISH INSTALLING EXHAUST DUCTS, FANS, INTERLOCK WITH A/C UNITS 2) PROVIDE MINIMUM 1" CLEARANCE FOR WOOD AND INSULATION ON WATER HEATER VENTS 3) NEED TO TEST DUCT SMOKE DETECTORS |
|
08/06/2004 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*/ 1) FINISH WORK IN EQUIPMENT ROOM |