Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T03CM03878
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2004 | PLUMBING - INTERMEDIATE | Approved | ||
08/10/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
08/09/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) H20 PIPING IN BLDG WATER TEST OK 2) SUPPORT PIPING AT MIXING VALVES 3) T & P'S TO GRAVITY DRAIN TO APPROVED RECEPTOR 4) FINISH INSULATION AT MIXING VALVES 5) INSTALL BACKFLOW DEVICES FOR PLAN OR HAVE STAMPED LETTER FROM ENGINEER OK FOR SMALLER SIZE | |
08/06/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) 4" TO 8" NORTH WEST CORNER OVERFLOW RAIN DRAIN WATER TEST OK. 4" TO 6" IN NORTH EAST CORNER AND 6" X 6" IN EAST 2ND AREA SOUTH WATER TEST OVERFLOW RAIN DRAIN. 2" OVERFLOW RAIN DRAINS ON LOWER EAST (NORTH) INTO 3" PIPING WATER TEST OK 2) NEED TO SEE ALL RAIN DRAINS EXCEPT 3 SETS ON SOUTH WEST END 3) NEED TO SEE UPPER NORTH EAST OVERFLOW AT COUNTER. AND ALL OVERFLOWS ON SOUTH SIDE OF ENTRY, PLUS TOP OF ENTRY 4) CORRECT HANGERS AT WEST CENTER RAIN DRAIN LOCATION 5) HAVE REVISED ROOF DRAIN PLAN ON SITE | |
08/05/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) COMPLETE ALL WORK THEN CALL FOR INSPECTION 2) PROVIDE VIEWING ACCESS TO ALL PIPING AT TIME OF INSPECTION | |
08/02/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WATER TEST WASTE AND VENT FOR POOL AREA SHOWER, 2 FLOOR DRAINS AND 1ST FLOOR SINK IN POOL EQUIPMENT ROOM THRU ROOF OK | |
07/29/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 1) WASTE AND VENT THRU ROOF AT EWC SOUTH LOBBY AREA OK 2) H20 PIPING FOR EWC SOUTH LOBBY AREA OK 3) (3) 4" OVERFLOW RAIN DRAINS ON WEST SIDE OF BLDG CENTER TO SOUTH WATER TEST OK 4) (1) NEED TO VIEW PIPING AT NEXT INSPECTION | |
07/26/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/20/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :WASTE AND VENT FOR EWC ON 2ND FLOOR VENT THAN ROOF WATER OK SOUTH LOCATION WATER PIPING FOR THIS AND MAIN PIPING FOR NORTH EAST AREA BACK TO OVERHEAD AT NORTH POOL AREA WALL AIR TEST OK AIR OR WATER TEST TO ROOF AND PROVIDE ACCESS TO ALL PIPING AND SUPPORTS |
|
07/14/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
07/09/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ 1) BE SURE YOU HAVE SOMETHING FOR INSPECTION, READY WHEN YOU CALL IN | |
06/28/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ WASTE AND VENT THRU ROOF IN TWO UNISEX RESTROOMS 145 & 146 AND DRY STORAGE 144 AND JUICE BAR 143 WTR TEST OK. H20 AIR TEST IN WALL THIS AREA OK. | |
06/24/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ WTR TEST THRU ROOF ON 2 EWF WASTE AND VENT ON COLUMN LINE 'C' AND H2O AIR TEST OK. | |
06/23/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*/ ABOVE HARD CEILING FROM SPINNING ROOM SOUTH OK. | |
06/21/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/21/2004 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/17/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/08/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
06/03/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
06/02/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ WASTE AND VENT THRU ROOF WTR TEST JANITOR 122, MENS AND WOMENS 120A AND 120 OK. H2O PIPING AIR TEST MENS AND WOMENS 120A AND 120 STUBBED OUT OF WALL INTO CEILING. | |
06/01/2004 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
05/28/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ WTR TEST ON WASTE AND VENT THRU ROOF MENS 107, VETIBULE 106, MENS 108, OK. H2O TEST THESE AREAS 60 PSI AIR TEST STUBBED INTO HALL AT WTR MAINS OK. NEED CITY APPROVED DRAWING OF H2O ISOMETRIC FOR MENS 109, URINALS AND LAVS. | |
05/13/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ 60 PSI AIR TEST ON SHOWER VALVES IN WOMENS SHOWERS STUBBED OUT OF STALLS (7) LOCATIONS OK. EXPOSE ALL PIPING AND HAVE PRESSURE TEST ON PIPING. | |
05/11/2004 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :*/ H2O TO 8 SHOWERS IN MENS 107 - 60 PSI AIR TEST OK. |