Permit: T03CM03878

Parcel: 12801003A


Addresses:

240 S WILMOT RD


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T03CM03878

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/08/2004 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*/ 1) WATER TEST ON POOL AREA DRAIN IN DECK AROUND POOL OK
07/06/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) 30 PSI AIR TEST FROM METER LOCATION TO OVERHEAD IN POOL EQUIPMENT ROOM 2 1/2" PER PLAN
07/01/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ PIPING MUST HAVE MIN. 1/8" PER FOOT FALL CORRECT DRAINAGE FITTINGS SHALL BE USED. 10' HEAD ON WTR TEST SHALL BE IN PLACE.
06/29/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/28/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/25/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*/ 1) PROVIDE APPROVED DRAINAGE FITTINGS AT ALL LOCATIONS. 2) PROVIDE UPPER TERMINAL FULL SIZE CLEAN OUTS ON ALL RUNS. 3) ALL PIPING TO BE RUN AT ΒΌ" PER FOOT FALL. 4) PIPING AT DRINKING FOUNTAIN CROSSING TO NOT INTERFERE WITH DRAINAGE.
06/24/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/23/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*/ ADDITION OF FLOOR C.O. IN POOL EQUIP. ROOM WTR TEST ON POOL EQUIP. DRAINAGE OK.
06/21/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
06/02/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
02/12/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 4" POOL EQUIPMENT BLD DRAIN 5' OUTSIDE BLD WEST, 2-4X3 COMBO STUBS FOR POOL AREA DRAINS, WEST TO 2-4" FLOOR SINKS, 1-3" FLOOR SINK. WATER TEST APPROVED.
01/30/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ WTR TEST ON REMAINDER OF UNDERGROUND WASTE AND VENT APPROVED ON SANITARY DRAINAGE. WILL NEED TO SEE ALL UNDERGROUND RAIN DRAINAGE AND POOL DRAINAGE.
01/21/2004 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection 0000*/ 1) WATER TEST ON 4" BLDG DRAIN FROM POINT OF TIE-IN TO 6" AT 5.3 + 6 NORTH TO GIRLS RESTROOM 146 AND 2" TO EDF-1 AT 2.7 + C
01/20/2004 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection 0000*