Inspection History Details
Inspection Status: Approved
Inspection History: STEM WALL/RETAINING WALL
Permit Number - T03CM03878
Inspection Description - STEM WALL/RETAINING WALL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/29/2004 | STEM WALL/RETAINING WALL | Approved | IVRS - Inspection :* | |
03/02/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* REMAINING STEMS IN SHOWER AREA | |
02/17/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* WEST STEMS POOL AREA | |
02/13/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* SHOWER SREA OK PER RFI | |
02/12/2004 | STEM WALL/RETAINING WALL | Denied | IVRS - Inspection 0999* REF 9/S6.0 THIS CURB IS DESIGNED MONOLITHIE WITH SLAB. I BELIEVE THIS IS TO CREATE A LARGE "SHOWER PAN"- WITHOUT AN RFI FROM ARCHITECT ALLOWING SPLIT POURS THEN IT NEEDS TO CONFORM TO PLAN. | |
01/22/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* POP OUTS @ EAST SIDE. | |
01/20/2004 | STEM WALL/RETAINING WALL | Partial Approval | IVRS - Inspection 0000* H-3 AROUND TO H-8 PERIMETER STEM |