Permit: T03CM03865

Parcel: 13331159T


Addresses:

8800 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T03CM03865

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/09/2008 PLUMBING - FINAL Approved
12/24/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ APPROVED FULL SIZE PIPING UP TO INLET OF ALL BACKFLOW DEVICES. USE APPROVED MATERIAL FOR SECURING PIPING UNDER LAVS.
12/22/2003 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 1) PLEASE PROVIDE BACKFLOW CERTIFICATIONS ON ALL TESTABLE DEVICES. 2) PLEASE PROVIDE APPROVED FULL SIZE PIPING TO ALL BACKFLOW DEVICES. 3) PLEASE PROVIDE BACKFLOW DEVICES PIPED IN MANNER TO RESTRICT BACKFLOW FROM OTHER EQUIPMENTS. EACH PIECE OF EQUIPMENT REQUIRES A SEPERATE BACKFLOW DEVICE I.E. 2-CARBONATORS, 2- BACKFLOW DEVICES. PIPE DRAINS FROM BACKFLOW DEVICES TO APPROVED DRAIN. 4) PLEASE SUPPORT H20 PIPING UNDER ALL LAVS IN RESTROOMS AND INSULATE PROPERLY.