Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
| Date |
Description |
Inspector |
Results |
Comments |
| 04/05/2004 |
EXT METAL CLIPS/EXT SHEATHING |
|
Approved |
IVRS - Inspection 0000* |
| 10/17/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Partial Approval |
IVRS - Inspection 0000* 1) PROVIDE TRUSS CALC'S 2) OK TO COVER ROOF |
| 10/16/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0145*/ 1) RECALL |
| 10/14/2003 |
EXT METAL CLIPS/EXT SHEATHING |
|
Denied |
IVRS - Inspection 0999*/ 1) OVERSPAN OF DOUBLE TOP PLATE ABOVE HEADERS FOR WINDOWS IN GARAGE. ADD CRIPPLE STUDS 2) OSB ROOF SHEATHING MUST BE APPLIED WITH GRAIN PERPENDICULAR TO TRUSSES 4 PANELS 3) LEDGER BUTT SPLICES MUST OCCUR ON STRUCTURAL MEMBERS 4) NO CITY APPROVED TRUSS DRAWINGS ON SITE 5) PROVIDE LEDGER DETAIL THAT IS NOT SHOWN ON 3/D2 6) PROVIDE SHEAR PANEL DETAILS TO INCLUDE TYPE OF MATERIAL NAIL SIZE AND NAIL PATERN AS WELL AS HOLDOWN REQUIREMENT 7) SHEAR MUST BE NAILED AT ALL EDGES AND SEAMS AND TO ALL SUPPORTING STUDS 8) SUPPORTING POSTS MUST EQUAL WIDTH OF BEAM SUPPORTED 9) ONE ROOF PANEL NOT NAILED |