Permit: T03CM03851

Parcel: 116155090

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T03CM03851

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/29/2003 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
09/26/2003 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*/ 1) ALREADY COVERED 2) NO ONE ON SITE TO ANSWER QUESTIONS ON CHANGES SUCH AS PLAN SHOWS NEW A/C 100 AMP PANEL FED OFF OF NEW 100A METER AND DISCONNECT. PLEASE RECALL AND HAVE CONTRACTOR MEET INSPECTOR
09/12/2003 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*