Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 07/13/2004 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection :* |
| 03/04/2004 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0245* / 1) INSTALL A PERMANENET ADDRESS LABEL, SCREWED OR RIVITED TO ENCLOSURE. 2) INSTALL BOND BUSHING AT SERVICE NIPPLE BOTH SIDES, AND RISER CONDUIT. 3) GROUND 12X12 J-BOX, USE APPROVED FITTINGS, REDUCING WASHERS, BUSHINGS ETC. 4) BOND BLDG STEEL, COLD WATER PIPING TO SERVICE GROUNDING ELECTRODE SYSTEM. 5) SUPPORT CONDUIT WITHIN 3' OF TERMINATIONS, EVERY 10'. 6) INSTALL GROUND TAILS IN METAL BOXES THRU OUT. 7) 6" of make-up conductors in each device box. 8)PLUG ALL UNUSED OPENINGS IN BOXES, FIXTURES. |
| 03/03/2004 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0920* |