Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T03CM03830
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2004 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/15/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000*/ 1) PVC CONDUITS LAYING ON GRID PLEASE SUPPORT. 2) CONDUITS TO BE SUPPORTED AS PER CODES 348-13 AND 300-11. CONDUIT NOT TO SUPPORTED OFF OF CONDUITS. 3) NEW T-BAR GRID - FIXTURES TO BE ATTACHED TO GRID. 4) SUPPORT FLEX CONDUIT AS PER CODES 351 AND 300-11. 5) BOXES IN CEILING TO HAVE SUPPORT WIRES. 6) ALL BOXES MORE THAN ΒΌ" FROM BOX TO SURFACE TO HAVE AN APPROVED EXTENDER RING - NON COMBUSTABLE - 370-20. METAL NOT APPROVED DEVICE AND LIGHT BOXES. | |
02/05/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*/ 1) OK TEMP C OF O 2ND FLOOR |