Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/25/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 04/15/2004 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*/ 1) PVC CONDUITS LAYING ON GRID PLEASE SUPPORT. 2) CONDUITS TO BE SUPPORTED AS PER CODES 348-13 AND 300-11. CONDUIT NOT TO SUPPORTED OFF OF CONDUITS. 3) NEW T-BAR GRID - FIXTURES TO BE ATTACHED TO GRID. 4) SUPPORT FLEX CONDUIT AS PER CODES 351 AND 300-11. 5) BOXES IN CEILING TO HAVE SUPPORT WIRES. 6) ALL BOXES MORE THAN ΒΌ" FROM BOX TO SURFACE TO HAVE AN APPROVED EXTENDER RING - NON COMBUSTABLE - 370-20. METAL NOT APPROVED DEVICE AND LIGHT BOXES. |
| 02/05/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*/ 1) OK TEMP C OF O 2ND FLOOR |