Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/01/2004 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection 0000*/ ALL CORRECTIONS MADE - OK FOR FINAL C OF O. |
| 03/25/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PLANS SHOW RETURN DUCT RELOCATED TO ALLOW ACCESS TO SERVICE EXISTING FAN COIL. THIS STILL HAS NOT BEEN DONE. RELOCATE ELEC. CONDUITS BLOCKING ACCESS TO OTHER FAN COIL. INTERLOCK MAKE-UP AIR WITH KITCHEN EXHAUST. RECALL FOR INSP. |
| 02/19/2004 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) FAN COIL IN ATTIC HAS NO ACCESS FOR SERVICE. 2) EXHAUST DUCT SMASHED IN ATTIC - REPLACE AS NEEDED. 3) SUPPLY DUCT NOT CONNECTED. 4) NEED TO SEE KITCHEN EQUIPMENT INSTALLED AND EXHAUST FAN INTERLOCKED WITH MAKE UP AIR UNIT. RE-CALL FOR INSPECTION. |