Permit: T03CM03808

Parcel: 13606013D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/01/2004 MECHANICAL - FINAL Approved IVRS - Inspection 0000*/ ALL CORRECTIONS MADE - OK FOR FINAL C OF O.
03/25/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ PLANS SHOW RETURN DUCT RELOCATED TO ALLOW ACCESS TO SERVICE EXISTING FAN COIL. THIS STILL HAS NOT BEEN DONE. RELOCATE ELEC. CONDUITS BLOCKING ACCESS TO OTHER FAN COIL. INTERLOCK MAKE-UP AIR WITH KITCHEN EXHAUST. RECALL FOR INSP.
02/19/2004 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) FAN COIL IN ATTIC HAS NO ACCESS FOR SERVICE. 2) EXHAUST DUCT SMASHED IN ATTIC - REPLACE AS NEEDED. 3) SUPPLY DUCT NOT CONNECTED. 4) NEED TO SEE KITCHEN EQUIPMENT INSTALLED AND EXHAUST FAN INTERLOCKED WITH MAKE UP AIR UNIT. RE-CALL FOR INSPECTION.