Inspection History: PLUMBING - FINAL

Permit Number - T03CM03808

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2004 PLUMBING - FINAL Approved IVRS - Inspection 0000*/correction made.
04/08/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ PLEASE READ NOTE #2 FROM PREV. INSP. DATED 4/1/04, COMPLY OR PROVIDE LISTING FOR SODA DISPENSOR
04/01/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ PROVIDE CERTIFICATIONS OF BACKFLOW DEVICES. 1) INDIRECT DRAINS FROM SODA DISPENSER TO BE TRAPPED BECAUSE OF EXCESS OF 5' IN LENGTH. 2) SODA DISPENSER TO HAVE SEPERATE WTR SOURCE FOR WTR DISPENSER. THIS IS NOT REQUIRED TO BE BACKFLOW PROTECTION. WTR SOURCE TO LEMONADE IS TO BE BACKFLOW PROTECTED AS IS CARBONATOR. 3) WTR HTR T&P TO BE A.S.M.E. CERTIFIED. 4) PROVIDE PROPER CONNECTION TO SINKS IN REAR, MISSION STYLE COUPLING IS NOT APPROVED FOR THIS APPLICATION.
03/25/2004 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*/ 25 PSI TEST FROM METER EXISTING 2" PIPING SECURED UNDERSLAB UP INTO BLD TO PIPING AS PER APPROVED PLAN. PROVIDE SEPERATE WTR SOURCES FOR SODA MACHINE DISPENSERS WITH PROPER BACKFLOW PROTECTION WHEN REQUIRED. ICE MACHINE TO HAVE DRAINS TO DRAIN WITH PROPER AIR GAP AT FLOOR SINK. WTR HTR T&P TO BE OPERABLE AND RIDGID PIPED TO DRAIN. CAP ALL UNUSED H20 SUPPLIES OR DEAD LINES. PROVIDE FLOW CONTROL ON GREASE TRAP INLET WITH VENT.